NSN 5925-00-620-5844 Circuit Breaker manufactured by Dla Land And Maritime, General Electric Company is available within ASAP Part Service’s ready-to-ship inventory. Owned and operated by ASAP Semiconductor, ASAP Part Services has over 6 billion parts within its inventory including 6319452G2L, 6319482G2L, ALB-10 150. ASAP is committed to streamlining the parts procurement process for our customers. We make it easy for our customers to search through billions of parts to find the exact part they are looking for.
A dedicated ASAP account manager is ready to help solve any procurement issues or needs that a customer may have. As a company we are quick and responsive meaning we can deliver a part within an AOG timeframe. Quality control is at the center of all that we do. Each and every NSN 5925-00-620-5844 part is subject to numerous quality checks that are designed to screen out any part imperfections or validity issues. Subject a request for quote for NSN 5925-00-620-5844 part today and allow us to simplify your procurement process.
Alternative NSN: 5925-00-620-5844 |
Item Name:Circuit Breaker |
FSG: 59 Electrical and Electronic Equipment Components |
Federal Supply Class (FSC): 5925 Circuit Breakers |
NCB Code: USA (00) |
Manufacturers: Dla Land And Maritime , General Electric Company |
Part No Part No
|
Manufacturer NSN Parts
|
Item Name Item Name
|
QTY QTY
|
RFQ RFQ
|
---|---|---|---|---|
6319452G2L | Dla Land And Maritime | circuit breaker | Avl | RFQ |
6319452G2L | General Electric Company | circuit breaker | Avl | RFQ |
6319482G2L | General Electric Company | circuit breaker | Avl | RFQ |
ALB-10 150 | General Electric Company | circuit breaker | Avl | RFQ |
ALB-10 150 | Dla Land And Maritime | circuit breaker | Avl | RFQ |
DMS 79009B | General Electric Company | circuit breaker | Avl | RFQ |
DMS 79009B | Dla Land And Maritime | circuit breaker | Avl | RFQ |
MIL-C-17588 | Dla Land And Maritime | circuit breaker | Avl | RFQ |
MIL-C-17588 | General Electric Company | circuit breaker | Avl | RFQ |
TN231150 | General Electric Company | circuit breaker | Avl | RFQ |
TN231150 | Dla Land And Maritime | circuit breaker | Avl | RFQ |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 5.000 INCHES NOMINAL |
ADAT | BODY WIDTH | 4.750 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.625 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.688 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.250 INCHES NOMINAL |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, SINGLE THROW, NORMALLY CLOSED |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.312 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 4.625 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 20 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 150.0 AMPERES AC ALL LOCATIONS AND 150.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 AC ALL LOCATIONS AND 125.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS AND 5000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 ALL LOCATIONS |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 3600.000 NOMINAL ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
CQJX | NOMINAL THREAD SIZE | 0.250 INCHES |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | EXTERNAL AT POLE TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 210.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CRTK | SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC AND 10.0 DC |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC AND 125.0 DC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TEST | TEST DATA DOCUMENT | 81349-MIL-C-17588 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTI |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
ZZZK | SPECIFICATION/STANDARD DATA | 81349-MIL-C-17588 GOVERNMENT SPECIFICATION |
All Orders are Fulfilled in the U.S.A.
All shipments must comply with U.S.A export laws.
No exceptions.
The only independent distributor
with a NO CHINA SOURCING Pledge
“We Proudly Support Intrepid Fallen Heroes Fund that serves United States Military Personal experiencing the Invisible Wounds of War : Traumatic Brain Injury (TBI) and Post Traumatic Stress (PTS). Please visit website (www.fallenheroesfund.org) and help in their valiant effort”.
Remember Us the Next Time You’re Looking for NSN Parts. We Can Get You Some of the Quickest and Most Competitive Quotes In the Industry.
Request for Quote