NSN 5925-01-031-9909 Circuit Breaker manufactured by Navair And Navsea Managed, Eaton Corp, Spd Electrical Systems Inc, Pacord Inc, L 3 Services Inc is available within ASAP Part Service’s ready-to-ship inventory. Owned and operated by ASAP Semiconductor, ASAP Part Services has over 6 billion parts within its inventory including 2664992-1, 313C682G19, AQB-A250 125NM. ASAP is committed to streamlining the parts procurement process for our customers. We make it easy for our customers to search through billions of parts to find the exact part they are looking for.
A dedicated ASAP account manager is ready to help solve any procurement issues or needs that a customer may have. As a company we are quick and responsive meaning we can deliver a part within an AOG timeframe. Quality control is at the center of all that we do. Each and every NSN 5925-01-031-9909 part is subject to numerous quality checks that are designed to screen out any part imperfections or validity issues. Subject a request for quote for NSN 5925-01-031-9909 part today and allow us to simplify your procurement process.
Alternative NSN: 5925-01-031-9909 |
Item Name:Circuit Breaker |
FSG: 59 Electrical and Electronic Equipment Components |
Federal Supply Class (FSC): 5925 Circuit Breakers |
NCB Code: USA (01) |
Manufacturers: Navair And Navsea Managed , Eaton Corp , Spd Electrical Systems Inc , Pacord Inc , L 3 Services Inc |
Part No Part No
|
Manufacturer NSN Parts
|
Item Name Item Name
|
QTY QTY
|
RFQ RFQ
|
---|---|---|---|---|
2664992-1 | Navair And Navsea Managed | circuit breaker | Avl | RFQ |
2664992-1 | Eaton Corp | circuit breaker | Avl | RFQ |
313C682G19 | Eaton Corp | circuit breaker | Avl | RFQ |
313C682G19 | Navair And Navsea Managed | circuit breaker | Avl | RFQ |
AQB-A250 125NM | Navair And Navsea Managed | circuit breaker | Avl | RFQ |
AQB-A250 125NM | Eaton Corp | circuit breaker | Avl | RFQ |
AQB-A250-125AMP | Eaton Corp | circuit breaker | Avl | RFQ |
AQB-A250-125AMP | Navair And Navsea Managed | circuit breaker | Avl | RFQ |
ETN5953 | Spd Electrical Systems Inc | circuit breaker | Avl | RFQ |
ETN5953 | Pacord Inc | circuit breaker | Avl | RFQ |
ETN5953 | L 3 Services Inc | circuit breaker | Avl | RFQ |
ETN5953 SEE REMARKS REPLACEMENT | L 3 Services Inc | circuit breaker | Avl | RFQ |
S313C682G19 | Navair And Navsea Managed | circuit breaker | Avl | RFQ |
S313C682G19 | Eaton Corp | circuit breaker | Avl | RFQ |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 11.000 INCHES MAXIMUM |
ADAT | BODY WIDTH | 9.000 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 9.875 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 3.000 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 9.875 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 3.000 INCHES NOMINAL |
AGAV | END ITEM IDENTIFICATION | CIRCUIT BREAKER AAQB 250FR 125TRP 1950-4100TR |
AJEC | BOSS HEIGHT | 0.250 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 9.312 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
CMLP | THREAD QUANTITY PER INCH | 20 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 125.0 AMPERES AC ALL LOCATIONS AND 125.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC ALL LOCATIONS AND 20000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQJX | NOMINAL THREAD SIZE | 0.250 INCHES |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 MAXIMUM NOT APPLICABLE ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
All Orders are Fulfilled in the U.S.A.